Cummins C1000D5
- Standby:
- 1041 kVA
- Voltage:
- 380‑440 V
- Prime:
- 939 kVA
- Frequency:
- 50Hz
- Engine:
- Cummins QST30‑G3
- Amps Per Phase:
- 1503
- Alternator:
- Stamford S6E
- Control Panel:
- Cummins PowerCommand 3.3
The Cummins C1000D5 is a heavy-duty open diesel generator delivering 1041 kVA standby and 939 kVA prime power at 50 Hz. Featuring a Cummins QST30‑G3 V12 engine with turbocharging and after‑cooling, paired with a Stamford S6E alternator. Equipped with a PowerCommand 3.3 control panel for automatic start/stop, comprehensive diagnostics, and protection.
Engine Specs
Engine Model
QST30‑G3 (V12, turbocharged and after‑cooled)
Rated Speed
1 500 rpm
Bore × Stroke
140 × 165 mm
Lube Oil Capacity
133 L
Overspeed Limit
1 725 rpm ±50
Governor Type
Electronic
Starting Voltage
24 V DC
Gross Engine Power (Standby)
895 kWm
Gross Engine Power (Prime)
806 kWm
Compression Ratio
14 : 1
Regenerative Power
58 kW
Emission Level
Unregulated
Alternator Specs
Model
Stamford S6E
Insulation Class
H
IP Rating
IP23
Control Panel Specs
Controller Model
Cummins PowerCommand 3.3
Display
128×64 pixel backlit LCD
Battery Operation
12 V and 24 V supported
Fault Sensors
Over/Under voltage, Overcurrent, Engine faults
AMF Function
Auto Mains Failure with event logging
Fuel & Consumption
Standby Consumption @¼ load
55 L/hr
Standby Consumption @½ load
105 L/hr
Standby Consumption @¾ load
154 L/hr
Standby Consumption @full load
204 L/hr
Prime Consumption @¼ load
51 L/hr
Prime Consumption @½ load
94 L/hr
Prime Consumption @¾ load
139 L/hr
Prime Consumption @full load
184 L/hr
Max Fuel Flow
550 L/hr
Cooling & Air
Combustion Air Flow (Standby)
56.1 m³/min
Combustion Air Flow (Prime)
51.9 m³/min
Coolant Capacity (with radiator)
169 L
Cooling System Air Flow
15.5 m³/sec
Ambient Rating
40 °C
Exhaust
Exhaust Gas Flow (Standby)
163 m³/min
Exhaust Gas Flow (Prime)
146 m³/min
Exhaust Gas Temperature (Standby)
563 °C
Exhaust Gas Temperature (Prime)
541 °C
Max Back Pressure
10.2 kPa
Dimensions & Weight
Open Set (L×W×H)
4302 × 1702 × 2139 mm
Dry Weight (Open)
6304 kg
Standards & Accessories
Voltage Regulation
±1 % electronic
THD (Total Harmonic Distortion)
≤2 %
Gov. Type
Electronic
Battery Charger & Water Heater
Included as standard